Functional safety technical resource

What Is Safe Failure Fraction (SFF)?

Safe Failure Fraction (SFF) is the fraction of a subsystem's overall random hardware failure rate attributed to safe failures plus dangerous failures detected by diagnostics, using a consistent failure classification and boundary. SFF is used in particular functional-safety architectural-constraint methods; it is not the probability that a device will fail safely and does not by itself establish an achieved Safety Integrity Level (SIL).

Technical resource from Mangan Safety Instrumented Systems (Mangan SIS)

How SFF Is Determined

Under a common partition, SFF is represented as the safe failure rate plus the dangerous detected failure rate divided by the total safe and dangerous random hardware failure rate: (lambda S + lambda DD) / (lambda S + lambda DD + lambda DU). The expression is simple, but the classification work is not. Analysts must define the subsystem boundary, safety function, safe state, diagnostics, fault reaction, and whether each failure mode is safe, dangerous detected, or dangerous undetected. Mixing data developed for different boundaries or assumptions can make the resulting fraction misleading.

SFF Versus Diagnostic Coverage

Diagnostic coverage considers the detected share of dangerous failures for a diagnostic function and defined conditions. SFF has a broader numerator because it also includes failures classified as safe. Consequently, a device can have an SFF value that should not be read as its dangerous-failure diagnostic coverage. Proof-test coverage is different again: it concerns latent dangerous failures revealed by a specified periodic test. Keeping these measures separate prevents the same detected or safe failure contribution from being applied incorrectly in reliability models and architectural assessments.

Limits of an SFF Claim

SFF is meaningful only within the standard route and subsystem classification for which it is used. A high fraction does not describe the absolute dangerous undetected failure rate, common-cause exposure, proof-test effectiveness, systematic capability, or field suitability. It also does not compensate for incorrect failure-mode classification. Supplier documentation should therefore be reviewed for product variant, firmware, application restrictions, failure-rate source, diagnostic assumptions, and the stated boundary before an SFF value is adopted in a SIF design.

Best Practices for Reviewing Safe Failure Fraction

Trace every failure-rate category to a controlled failure-mode analysis or equivalent evidence. Confirm that the safe state and dangerous-failure criteria match the SIF application, and keep units, mission profile, diagnostic intervals, and repair assumptions consistent. Document the applicable IEC architectural route and whether the device or subsystem classification supports that route. Mangan SIS recommends reviewing SFF beside HFT, PFDavg or PFH, systematic capability, proof testing, and common-cause assumptions so that a fractional classification is not mistaken for a complete integrity assessment.

Mangan SIS project context

Apply Safe Failure Fraction (SFF) to documented SIS decisions

SFF may be used when evaluating architectural constraints for a sensor, logic-solver, or final-element subsystem under an applicable IEC route. Its role is specific: it helps categorize random hardware failure behavior for that architecture. It does not replace the SIF calculation or the evidence needed for systematic integrity and lifecycle execution.

Sources and scope

Use the source type that fits the decision

Standards

IEC 61508-2:2010 uses random hardware failure classification and architectural constraints within its hardware requirements. IEC 61511-1:2016 provides process-sector SIS requirements and routes that must be applied as written.

Guidance

IEC 61508-6:2010 provides guidance on applying IEC 61508 hardware concepts and calculation techniques. Project use should rely on controlled source documents and device evidence, not a glossary formula alone.

Regulation

OSHA 29 CFR 1910.119 does not define SFF or prescribe a minimum SFF. PSM applicability and mechanical-integrity duties should be evaluated separately for covered processes.

Mangan recommendation

Mangan SIS recommends accepting an SFF value only when its failure classifications, subsystem boundary, product configuration, diagnostic assumptions, data source, and applicable architectural route are documented and relevant to the SIF.

Primary references

Common questions

Clarifying Safe Failure Fraction (SFF)

Is Safe Failure Fraction the probability a device fails safely?

No. SFF is a ratio of classified random hardware failure rates within a defined boundary. It combines safe failures and dangerous detected failures in the numerator.

Is SFF the same as diagnostic coverage?

No. Diagnostic coverage focuses on detection of dangerous failures. SFF also includes safe failures and is used for a different architectural purpose.

Can SFF by itself determine SIL?

No. SFF may contribute to an architectural-constraint assessment under an applicable route. Quantitative performance, HFT, systematic capability, application restrictions, and lifecycle evidence remain separate.

Need a defensible verification basis?

Review the data, assumptions, and evidence behind your SIF calculation.

Contact Mangan SIS

Downloadable term reference

Download: Safe Failure Fraction (SFF) - Functional Safety Glossary PDF

Save or share this term-specific reference, including the answer-first definition, engineering review considerations, and primary-source references.

Download the Safe Failure Fraction (SFF) PDF
Scroll to Top