What Is Prior Use (Proven in Use)?

Prior use is an IEC 61511 process-sector route for selecting a safety instrumented system (SIS) device based on documented evidence from previous operation in sufficiently similar applications and environments. Proven in use is a related IEC 61508 concept with defined evidence requirements, including a specific route for certain pre-existing software elements. The phrases should not be treated as casual synonyms: the applicable standard, item type, claimed function, evidence period, configuration, and similarity to the intended use must be explicit.

Technical resource from Mangan Safety Instrumented Systems (Mangan SIS)

Prior use in the process sector

IEC 61511 permits selection based on prior use when the user has appropriate evidence that a device performs as required in comparable SIS applications. The basis is not that a product is familiar or has operated somewhere without a reported incident. It requires a defined population and service history, controlled identification, relevant failure and demand data, comparable environmental and process conditions, and management practices capable of finding and recording failures.

Why proven in use is not an interchangeable label

IEC 61508 uses proven-in-use concepts within its generic functional-safety framework, and IEC TS 61508-3-1 addresses a defined route for reusing certain pre-existing software elements. Those requirements and limitations are not automatically the same as IEC 61511 device selection based on prior use. The engineering record should name the governing route rather than combining the phrases into an undefined claim.

Evidence a defensible assessment needs

The package should identify the exact model, hardware and software revisions, safety function, configuration range, operating time or demands as appropriate, population, reported dangerous and safe failures, data-collection process, proof testing, maintenance, modifications, environments, and quality controls. It should also explain why the previous and intended applications are comparable and how systematic faults or under-reporting were considered.

Conditions that can break comparability

A new process medium, temperature range, vibration level, duty cycle, diagnostic configuration, firmware, accessory, installation method, proof-test procedure, maintenance practice, or safety function can make historical evidence less applicable. Obsolescence and manufacturer changes also matter. Changes should trigger documented review rather than automatic transfer of the original prior-use conclusion.

Mangan SIS project context

Apply Prior Use (Proven in Use) to documented SIS decisions

Use a prior-use assessment during device selection or continued-use review when the chosen IEC 61511 route relies on operating experience. Keep it separate from random failure-rate validation, systematic capability, certification, and the complete SIF verification. If using an IEC 61508 proven-in-use route, apply its specific scope and requirements instead of assuming the process-sector prior-use record is equivalent.

Sources and scope

Use the source type that fits the decision

Standards

IEC 61511-1 contains requirements for selecting devices based on prior use in process-sector SIS applications. IEC 61508 provides the generic functional-safety framework, while IEC TS 61508-3-1 defines a specific proven-in-use route for certain pre-existing software elements. The correct route depends on the item and application.

Guidance

ISA-TR84.00.04 Part 1 provides informative guidance on existing SIS and device-selection evidence, including prior use. It explains implementation context but does not relax the normative requirements or make undocumented operating history sufficient.

Regulation

OSHA 29 CFR 1910.119 does not make prior use or proven in use a standalone equipment-acceptance rule. For covered processes, applicable process safety information, mechanical-integrity, procedure, deficiency-correction, and management-of-change duties continue to apply.

Mangan recommendation

Mangan SIS recommends naming the governing standard route, defining the evidence population and collection method, documenting application similarity, and recording limitations and change triggers. Do not describe familiarity, a vendor installed base, or absence of reported incidents as sufficient proof by itself.

Common questions

Clarifying Prior Use (Proven in Use)

Are prior use and proven in use the same thing?

They are related but should not be treated as exact synonyms. Prior use is a defined IEC 61511 process-sector device-selection route; IEC 61508 proven-in-use routes have their own scopes and evidence requirements.

Is long operating history enough for a prior-use claim?

No. The evidence must be relevant, controlled, and comparable to the intended safety function, configuration, environment, duty, testing, maintenance, and data-collection quality.

Does prior use eliminate the need for SIF verification?

No. Prior use supports device selection. The complete SIF still requires requirements traceability, architecture and random-hardware verification, systematic controls, integration, validation, operation, and maintenance.

Need lifecycle assurance?

Connect lifecycle requirements, responsibilities, and evidence to your SIS program.

Contact Mangan SIS

Downloadable term reference

Download: Prior Use (Proven in Use) - Functional Safety Glossary PDF

Save or share this term-specific reference, including the answer-first definition, engineering review considerations, and primary-source references.