Functional safety technical resource
What Is Hardware Fault Tolerance (HFT)?
Hardware Fault Tolerance (HFT) is the ability of a hardware architecture to continue performing a required safety function when specified dangerous hardware faults occur. In common functional-safety notation, HFT 0 means no dangerous hardware fault is tolerated before loss of the function, while HFT 1 means one such fault can be tolerated; HFT is an architectural property, not a complete Safety Integrity Level (SIL) result.
Technical resource from Mangan Safety Instrumented Systems (Mangan SIS)
How HFT Relates to SIF Architecture
HFT depends on how components and channels are arranged and on which faults are included in the analysis. A single-channel subsystem commonly has no tolerance to a dangerous fault that disables its safety action. A properly implemented multi-channel architecture may tolerate one or more dangerous faults, but only if the channels, voting logic, shared elements, and fault response actually preserve the required function. The HFT conclusion should therefore be derived from the defined safety function and failure paths, not from the channel count or a product label alone.
HFT, Redundancy, and Independence
Redundancy provides additional elements; it does not automatically provide the intended fault tolerance. Shared impulse lines, power supplies, environmental exposure, software, maintenance practices, or final-element dependencies can defeat an apparently redundant design. Voting can also introduce behavior that must be modeled, including how detected faults are handled and whether degraded operation is permitted. HFT assessment should identify common elements and credible common-cause failures so that the claimed tolerance reflects the whole subsystem boundary.
Architectural Constraints and Quantitative Verification
Functional-safety standards use architectural constraints alongside quantitative failure-performance calculations. For IEC 61511 hardware architecture, the analysis should identify whether Route 1H or Route 2H applies and evaluate HFT using the route-specific device, failure-data, and architectural evidence. Conversely, adding fault tolerance does not eliminate the need to evaluate PFDavg or PFH, systematic capability, diagnostic behavior, proof testing, and repair. The conclusions should remain separate so a result in one area is not presented as evidence for every other requirement.
Best Practices for HFT Evaluation
Start with a functional block diagram that shows the complete SIF path and all shared utilities or interfaces. Define the dangerous failure criterion, identify the minimum cut sets that defeat the safety action, and test the HFT claim against credible detected and undetected faults. Document voting, degraded-mode restrictions, repair expectations, bypasses, and common-cause assumptions. Mangan SIS recommends confirming the as-built architecture and field practices because undocumented shared dependencies or maintenance bypasses can invalidate an HFT conclusion made from a simplified drawing.
Mangan SIS project context
Apply Hardware Fault Tolerance (HFT) to documented SIS decisions
HFT is evaluated during SIS architecture selection and verification for sensing, logic-solver, and final-element subsystems. It helps determine whether the architecture meets the applicable constraints for the intended SIL and device basis. This page explains the term; detailed project decisions require the applicable standard route, equipment evidence, and site-specific SIF design.
Continue the technical trail
Use these related definitions to follow the specific design or lifecycle relationship: Voting Architecture (1oo1, 1oo2, and 2oo3), Beta Factor, Common Cause Failure.
Sources and scope
Use the source type that fits the decision
Standards
IEC 61508-2:2010 contains hardware requirements and architectural-constraint provisions for E/E/PE safety-related systems. IEC 61511-1:2016 applies process-sector requirements to SIS hardware architecture.
Guidance
IEC 61511-2:2016 provides process-sector application guidance. The applicable architectural route and device classification should be confirmed from controlled standards and project evidence rather than inferred from a summary.
Regulation
OSHA 29 CFR 1910.119 does not prescribe an HFT value. For covered processes, design information, mechanical-integrity practices, and management of change may provide relevant regulatory context for SIS architecture and maintenance.
Mangan recommendation
Mangan SIS recommends evaluating HFT from the full SIF failure path, including shared utilities, voting, bypasses, degraded operation, repair behavior, and common-cause exposure—not merely counting installed channels.
Primary references
- IEC 61508-2:2010 publication record (Hardware standard)
- IEC 61508-4:2010 publication record (Definitions standard)
- IEC 61511-1:2016 publication record (Process-sector standard)
- OSHA 29 CFR 1910.119 — Process Safety Management (U.S. regulation)
Common questions
Clarifying Hardware Fault Tolerance (HFT)
Is HFT 1 the same as a 1oo2 architecture?
Not automatically. A 1oo2 arrangement may support tolerance of a dangerous channel fault, but the actual HFT depends on the defined function, voting, shared elements, failure modes, and how faults are handled.
Does higher HFT always mean higher SIL?
No. HFT is one architectural attribute. SIL capability also depends on the applicable architectural constraints, quantitative failure performance, systematic capability, lifecycle activities, and application-specific evidence.
Can redundancy fail to improve HFT?
Yes. Shared dependencies or common-cause mechanisms can allow one condition to disable multiple channels. Independence and the complete subsystem boundary must be evaluated.
Evaluating an SIS architecture?
Review voting, fault tolerance, dependencies, and lifecycle requirements for your SIF.
Downloadable term reference
Download: Hardware Fault Tolerance (HFT) - Functional Safety Glossary PDF
Save or share this term-specific reference, including the answer-first definition, engineering review considerations, and primary-source references.
Download the Hardware Fault Tolerance (HFT) PDF