Mangan SIS technical resources
Functional Safety Technical Resource Library
A technically grounded, answer-first functional safety glossary and reference to the terminology used to specify, design, verify, operate, test, and maintain safety instrumented functions (SIFs) and safety instrumented systems (SISs) in process-industry applications.
Start with the definition
Clear language for lifecycle decisions
Functional-safety work depends on terms that mean the same thing across hazard studies, requirements, architecture, configuration, verification, proof testing, operations, and change control. This library provides concise, answer-first explanations that connect each concept to its functional-safety role and lifecycle context.
Each entry distinguishes standards, guidance, regulation, and Mangan SIS engineering recommendations. It is technical orientation—not a substitute for the governing standard, approved safety requirements specification, hazard and risk analysis, calculations, operating data, procedures, or engineering review.
These 60 entries cover SIS architecture and response, risk reduction and performance, quantitative reliability concepts, testing, lifecycle governance, and operating controls. Use the entries to establish shared language before decisions are translated into project requirements and evidence.
A
ALARP is a Great Britain risk-reduction principle requiring risk to be reduced until further reduction would be grossly disproportionate to the sacrifice involved.
The modeled average frequency per operating hour at which a high-demand or continuous safety function experiences a dangerous failure.
B
The system that normally controls the process, distinct from independent SIS risk-reduction functions.
A parameter that assigns a stated portion of redundant-channel failure rate to common-cause failures in a simplified model.
Bowtie analysis maps threats and preventive barriers before a top event, then consequences and mitigation barriers after that event.
The controlled authorization, risk review, indication, tracking, and removal of a temporary impairment to a safety instrumented function.
C
A shared cause that can affect multiple components or channels assumed to be independent.
D
The rate of dangerous random hardware failures revealed by diagnostics or monitoring credited in the SIF model.
The rate of dangerous random hardware failures not revealed by the diagnostics credited in the SIF model.
A design approach in which removing a defined energy state initiates or permits a trip action.
The documented operating context and frequency assumptions for requests that require a SIF to act.
The rate or frequency assumption used to describe how often a defined protective function is requested.
A modeled measure of how effectively automatic diagnostics reveal specified dangerous failures.
The interval between online tests intended to detect specified faults in a subsystem with defined diagnostic coverage.
E
The equipment and defined actions used to move all or part of a process to a safer condition.
An emergency shutdown valve is an automated on-off valve that moves to a defined position when an emergency shutdown or safety function demands isolation, diversion, or depressurization.
Event tree analysis is a forward-branching method that starts with an initiating event and maps possible outcome sequences through the success or failure of subsequent functions.
F
Fail-open and fail-closed describe the valve position produced by a defined loss of signal or motive energy; the correct position depends on the process hazard.
Fail-safe describes a system property in which defined failures cause or preserve the specified safe condition for the identified hazard.
FMEA systematically identifies how an item or process can fail, the effects of each failure mode, and actions needed to address the findings.
A bottom-up analysis of component failure modes, their effects, and diagnostic detection, commonly used to develop classified failure-rate inputs.
The frequency of a defined failure type over stated exposure time for a specified item or population, with explicit units and assumptions.
Fault Tree Analysis models the combinations of events and conditions that can lead to a defined undesired top event.
The equipment that acts directly on the process when a safety function commands a protective response.
A fire and gas system detects hazardous fire, combustible-gas, or toxic-gas conditions and initiates alarms or mitigation actions defined for the facility.
The governance framework used to plan, assign, control, review, and document work that affects functional safety across the SIS lifecycle.
H
The ability of a hardware architecture to continue performing its safety function in the presence of a specified number of dangerous hardware faults.
A HIPPS is an instrumented protection system that detects excessive pressure and automatically isolates the pressure source before downstream limits are exceeded.
L
The SIS portion that evaluates defined safety inputs and commands required outputs.
M
The controlled process used to evaluate, authorize, document, and implement changes that can affect safety.
MTBF is the expected operating time between failures of a repairable item under stated conditions and a defined data boundary.
MTTR is commonly used for mean time to restoration, the expected elapsed time required to return an item to an operable state after failure.
P
A controlled limited movement of an automated on-off valve used to detect selected failure modes without completing the full safety stroke.
The average probability that a safety function will fail to perform its required action on demand, under stated assumptions.
A documented readiness review before introducing hazardous chemicals or starting up affected process equipment.
An IEC 61511 device-selection route based on documented experience in sufficiently similar applications; distinct from IEC 61508 proven in use.
The time available between a defined hazardous condition and the point at which a consequence can occur without successful action.
The fraction of dangerous undetected failures that a specified proof-test procedure can reveal within a defined device or SIF boundary.
R
RAGAGEP is OSHA PSM terminology for recognized and generally accepted good engineering practices applicable to process equipment and related inspection and testing.
A hardware failure caused by physical mechanisms that occurs unpredictably and can be described statistically for a defined population and context.
A reliability block diagram represents the combinations of successful block operation required for a system or function to succeed; it is a logic model, not a physical flow diagram.
A risk graph is a calibrated decision method that maps defined risk parameters through a fixed path to a required SIL or risk-reduction category for a safety function.
A risk matrix combines defined consequence and likelihood categories in a grid to support consistent risk ranking and decision-making.
A representation of risk reduction attributed to a protective function or layer within a documented method.
S
The fraction of a subsystem’s random hardware failure rate classified as safe or dangerous but detected, based on consistent failure classifications.
The defined process condition a safety function is intended to achieve or maintain for a specific hazardous event.
A defined protective function within an SIS for a specific hazardous event and required response.
An instrumented system that implements one or more safety instrumented functions.
A safety interlock automatically responds to a defined process or equipment condition by initiating a protective action; the name alone does not establish that it is a SIF.
The structured sequence of functional-safety activities from hazard assessment and specification through design, validation, operation, modification, and decommissioning.
A safety PLC is a programmable controller designed and assessed for use as the logic subsystem of a safety-related control system.
Safety-critical equipment is equipment whose failure, unavailability, or incorrect operation can materially contribute to a major hazard or defeat required prevention or mitigation.
The measurement portion of a safety function that detects the defined process condition.
An unintended protective action when the defined process demand has not occurred.
An IEC 61508 measure of confidence that an element’s systematic safety integrity supports requirements associated with a stated SIL.
A failure that recurs under particular conditions because of a fault introduced through specification, design, manufacture, installation, operation, or maintenance.
T
Tolerable risk is risk accepted within a defined context because it meets approved criteria and remains subject to required controls and further reduction principles.
The defined threshold or condition at which a safety function initiates its protective action.
U
The period during which an item’s failure-rate assumptions remain supportable under stated operating and environmental conditions.
V
The logic defining how many channels must act or agree for a subsystem response, such as 1oo1, 1oo2, or 2oo3.
Built around the lifecycle
Use the terms in the work where they matter
Define the function
Start with the hazardous scenario, safe state, trip condition, process safety time, and requirements that make a safety function testable.
Implement and validate
Keep requirements, logic, interfaces, testing, and commissioning evidence aligned as a system is configured and placed in service.
Operate and sustain
Use controlled testing, maintenance, observations, and change management to preserve the documented basis of the implemented function.
How source language is used
Standards, guidance, regulation, and recommendations are not interchangeable
Standards
IEC 61511 and its ANSI/ISA-61511 U.S. adoption provide the central process-industry SIS lifecycle and terminology context.
Guidance
IEC application guidance and ISA technical material can help teams interpret selected lifecycle concepts in a documented project context; they do not replace an approved project basis.
Regulation and Mangan recommendations
OSHA PSM applies only where its U.S. regulatory scope is met. Mangan recommendations are practical engineering considerations, not a claim of compliance or guaranteed performance.
Need application-specific support?
Discuss the requirements, lifecycle evidence, or field work behind your safety function.