Functional safety technical resource
What Is a Fire and Gas System (FGS)?
A Fire and Gas System (FGS) is a detection and response system used to identify fire, combustible-gas, or toxic-gas conditions and initiate defined alarms or mitigation actions. An FGS can include detectors, logic, annunciation, shutdown, isolation, ventilation, suppression, and emergency-response interfaces. It often mitigates a hazardous release after loss of containment, so its effectiveness cannot be evaluated from detector reliability alone.
Technical resource from Mangan Safety Instrumented Systems (Mangan SIS)
What an FGS Includes
An FGS may use point, open-path, flame, smoke, heat, or other detectors selected for the hazard and environment. Signals are evaluated by dedicated or shared logic and can drive local and control-room alarms, equipment shutdown, source isolation, ventilation changes, deluge, suppression, evacuation, or other emergency actions. The relevant function boundary includes more than the detector: placement, voting, communications, logic, output devices, utilities, human response, and the effectiveness of the mitigation action all influence the result. Different functions within one FGS can have different performance requirements.
Detection Coverage Is Scenario-Specific
Detector count is not a direct measure of protection. Coverage depends on release location and rate, material behavior, ventilation, congestion, weather, detector technology, obstruction, alarm threshold, field of view, and the scenario used for evaluation. Geographic coverage estimates where a detector can observe a target condition, while scenario coverage considers whether representative releases are detected. Both require documented assumptions and uncertainty. Placement should also account for access, calibration, maintenance, contamination, environmental limits, and the potential for one event to disable multiple detectors or communication paths.
How FGS Functions Relate to SIS
An FGS and a SIS can share performance-based concepts, but they are not automatically the same system. A typical SIF prevents or interrupts a defined process hazard before the hazardous event, while many FGS functions detect a release and mitigate its consequences. Some FGS controls, alarms, or interlocks may be assigned claimed risk reduction and implemented under requirements appropriate to that claim. The project should define whether each function is a general safeguard, a safety control or alarm, or a SIF rather than assigning one classification to the entire FGS.
Best Practices for FGS Lifecycle Management
Start with representative fire, combustible-gas, and toxic-gas scenarios, then define performance targets for detection coverage, availability, response time, mitigation effectiveness, voting, alarm handling, and human action. Document detector technology and placement assumptions, independence, common dependencies, environmental limits, cause-and-effect logic, testing, impairment controls, and restoration. Validate the complete path from exposure to credited response. Mangan SIS recommends periodically comparing detector alarms, proof-test findings, process changes, ventilation changes, and impairment history with the original design basis.
Mangan SIS project context
Apply Fire and Gas System (FGS) to documented SIS decisions
FGS engineering is used in process units, storage areas, compressor buildings, offshore facilities, and other locations where hazardous releases can develop into fire, explosion, or toxic exposure. This glossary page defines the system; project work must establish the actual scenarios, performance claims, detector mapping, mitigation effectiveness, and applicable code requirements.
Sources and scope
Use the source type that fits the decision
Standards
IEC 61511 establishes process-sector requirements for functions implemented as SIFs, but it does not make every FGS function a SIF. The required implementation basis depends on the function, claimed risk reduction, application-specific codes, and local authority requirements.
Guidance
ISA-TR84.00.07-2018 is an informative technical report for evaluating fire, combustible-gas, and toxic-gas system effectiveness. It addresses performance-based concepts such as risk, coverage, response, and mitigation; it is guidance and not itself a government regulation.
Regulation
OSHA 29 CFR 1910.119 identifies safety systems such as interlocks, detection, and suppression systems within process safety information for covered processes. It does not prescribe one FGS architecture, detector layout, or universal performance target, and other fire, building, environmental, or local requirements may apply.
Mangan recommendation
Mangan SIS recommends defining each FGS function by scenario, detection objective, claimed risk reduction, response path, and mitigation outcome, then validating the complete installed chain and controlling impairments through operation and change.
Primary references
- ISA-TR84.00.07-2018 – FGS effectiveness preview (Informative ISA guidance)
- ISA-84 Series of Standards – FGS and SIS resources (U.S. consensus standards and guidance)
- OSHA 29 CFR 1910.119 – Process Safety Management (U.S. regulation)
Common questions
Clarifying Fire and Gas System (FGS)
Is a fire and gas system always part of the SIS?
No. Some FGS functions may be implemented as SIFs or safety controls, while others are general alarms or safeguards. Classification depends on the defined function, risk claim, and applicable requirements.
What is the difference between detector coverage and detector reliability?
Coverage addresses whether the hazard can reach or be observed by a detector for the evaluated scenarios. Reliability addresses whether the detector and response path perform when required. An effective FGS needs an adequate basis for both.
Can an FGS prevent a hazardous release?
Some actions may isolate or limit an ongoing release, but many FGS functions first detect conditions after loss of containment and mitigate consequences. The claimed role must match the specific scenario and timing.
Need an evidence-based FGS design?
Connect hazard scenarios, detector coverage, mitigation actions, and lifecycle testing.
Downloadable term reference
Download: Fire and Gas System (FGS) – Functional Safety Glossary PDF
Save or share this term-specific reference, including the answer-first definition, engineering review considerations, and primary-source references.