Functional safety technical resource
What Is an FMEDA?
A failure modes, effects, and diagnostic analysis (FMEDA) is a structured, bottom-up evaluation of a device or subsystem that identifies component failure modes, determines their effects on the safety function, and assesses whether diagnostics detect them. Its outputs commonly support classification of safe, dangerous, detected, and undetected failure rates. An FMEDA is an input to engineering decisions; it is not a hazard analysis, a complete safety instrumented function (SIF) verification, or proof that the installed application meets its Safety Integrity Level (SIL) target.
Technical resource from Mangan Safety Instrumented Systems (Mangan SIS)
What an FMEDA produces
An FMEDA starts with an item boundary and intended safety function, then evaluates credible component failure modes and their local and end effects. Diagnostics are mapped to the failures they can detect, and the resulting rates are classified for use in reliability work. A useful report identifies the device variant, operating mode, assumed environment, data source, diagnostic test behavior, failure exclusions, and any design or user measures required for the results to remain valid.
How FMEDA differs from FMEA and SIF verification
A conventional FMEA identifies failure modes and effects but may not quantify failure rates or analyze diagnostic coverage. FMEDA adds diagnostic and quantitative classification work for the defined item. SIF verification has a broader boundary: it combines sensor, logic solver, final element, voting, common-cause, test, repair, demand-mode, and other assumptions to evaluate the complete function. No single component FMEDA closes that larger calculation.
Application assumptions can change the result
Published FMEDA data may depend on a specific model, revision, proof-test method, diagnostic configuration, process interface, environmental range, failure-rate source, and useful-lifetime assumption. An installed device can also have external elements—impulse lines, wiring, air supply, solenoids, actuators, accessories, or process connections—outside the manufacturer's analysis boundary. The verifier must reconcile those boundaries rather than copy headline values into a model.
How to review an FMEDA report
Confirm the report's authorship and revision; device and firmware match; safety function and safe-state assumptions; data confidence; failure classifications; diagnostic intervals and reactions; useful lifetime; proof-test procedures and coverage; and exclusions. Compare the classified rates with field experience and the safety manual. Differences should be resolved and documented before the values are used in a SIF calculation or maintenance strategy.
Mangan SIS project context
Apply Failure Modes, Effects, and Diagnostic Analysis (FMEDA) to documented SIS decisions
Use an FMEDA when selecting devices, reviewing vendor failure data, defining proof-test coverage, and assembling inputs to PFDavg or PFH verification. Preserve the report revision and every applied assumption in the calculation file. If the installed boundary or configuration differs, obtain a justified adjustment or use data appropriate to the actual application.
Continue the technical trail
Use these related definitions to follow the specific design or lifecycle relationship: Failure Rate (Lambda), Safe Failure Fraction (SFF), Diagnostic Coverage.
Sources and scope
Use the source type that fits the decision
Standards
IEC 61508-2 establishes requirements for E/E/PE safety-related elements, and IEC 61508-6 supplies application guidance and calculation examples. IEC 61511 requires process-sector SIF designs and verification to use appropriate data and assumptions. The standards do not make the possession of an FMEDA sufficient evidence for a complete SIF claim.
Guidance
ISA-TR84.00.02 is informative guidance for SIF SIL verification, including failure modes, failure rates, diagnostics, common-cause effects, and quantitative methods. An FMEDA report should be read together with the element's safety manual and the project's approved calculation basis.
Regulation
OSHA 29 CFR 1910.119 does not prescribe an FMEDA document. For covered processes, required process safety information, mechanical integrity, procedures, and change control remain distinct; an FMEDA can support engineering work but does not demonstrate regulatory compliance by itself.
Mangan recommendation
Mangan SIS recommends treating every FMEDA value as configuration- and assumption-dependent. Verify the device boundary, data source, diagnostics, proof-test coverage, useful lifetime, and exclusions before transferring rates into a SIF model, and retain the cross-reference to the exact report revision.
Primary references
- IEC 61508-2:2010 — E/E/PE safety-related system requirements (International standard)
- IEC 61508-6:2010 — application and calculation guidance (International standard guidance)
- ISA-TR84.00.02-2022 — SIF SIL verification preview (Informative ISA guidance)
- OSHA 29 CFR 1910.119 — Process Safety Management (U.S. regulation)
Common questions
Clarifying Failure Modes, Effects, and Diagnostic Analysis (FMEDA)
Is an FMEDA the same as an FMEA?
No. Both examine failure modes and effects, but an FMEDA adds explicit analysis of diagnostics and typically quantitative failure-rate classification for the defined device or subsystem.
Does an FMEDA prove that a SIF meets its SIL target?
No. It supplies data for part of the design. Complete verification must address all SIF subsystems, architecture, common cause, testing, repair, operating mode, application conditions, and the approved SRS.
Can vendor FMEDA rates be copied directly into a calculation?
Only after confirming that the model, revision, safety function, environment, diagnostics, proof test, useful lifetime, and analysis boundary match the installed application. Any mismatch needs a documented technical basis.
Need a defensible verification basis?
Review the data, assumptions, and evidence behind your SIF calculation.
Downloadable term reference
Download: Failure Modes, Effects, and Diagnostic Analysis (FMEDA) - Functional Safety Glossary PDF
Save or share this term-specific reference, including the answer-first definition, engineering review considerations, and primary-source references.
Download the Failure Modes, Effects, and Diagnostic Analysis (FMEDA) PDF