Functional safety technical resource

What Is Diagnostic Coverage in Functional Safety?

Diagnostic coverage is a modeled measure of how much of a defined class of dangerous failures is revealed by automatic diagnostics. It describes diagnostic effectiveness under stated assumptions; it is not the same as overall SIF availability, proof-test coverage, or achieved safety integrity.

Diagnostics reveal some failures between proof tests

Automatic diagnostics can identify certain faults while the SIF is in service, but they do not necessarily reveal every dangerous failure or demonstrate that the final element will perform the required action on demand. The relevance of a diagnostic claim depends on installed equipment and configuration.

The model needs an applicable basis

Device evidence, test behavior, fault response, repair assumptions, proof-test scope, and intervals must be considered together. A published value should not be carried into a model without checking the application conditions and whether the installed configuration matches the stated evidence.

Proof testing has a separate role

Proof testing and inspection can address failures that automatic diagnostics may not reveal. The documented test method should identify the functions, failure modes, and assumptions it addresses rather than assume high diagnostic coverage alone establishes adequate detection.

Mangan SIS project context

Apply the term to the documented safety function

Verify that diagnostic claims are applicable to the device, configuration, and use case; then align calculation inputs and proof-test procedures with the documented basis. Mangan SIS can support standards development, SIL verification, field testing, and proof-test procedures.

Sources and scope

Use the source type that fits the decision

Standards

IEC 61511-1:2016+AMD1:2017 provides the lifecycle framework; IEC 61508-2 and IEC 61508-6 include relevant hardware and application guidance concepts.

Guidance

IEC 61511 Parts 2 and 3 and applicable ISA-84 technical material provide guidance that must be applied to the documented project context.

Regulation

OSHA Process Safety Management applies only to covered U.S. processes. The applicability of a particular action should be determined within the owner’s PSM program.

Mangan recommendation

Use the approved SRS, hazard and risk analysis, design basis, operating data, test records, and management-of-change process to make project-specific decisions.

Common questions

Clarifying the term

Does high diagnostic coverage remove the need for proof testing?

No. Proof testing and inspection can address failures that automatic diagnostics may not reveal.

Can a published device value be used unchanged?

Only if equipment, configuration, application conditions, and model assumptions align with supporting evidence.

Is diagnostic coverage the same as PFDavg?

No. It is one modeled diagnostic concept; PFDavg is an average probability of failure on demand under stated assumptions.

Need application-specific context?

Discuss the requirements, evidence, or field work behind your safety function.

Contact Mangan SIS

Downloadable term reference

Download: Diagnostic Coverage — Functional Safety Glossary PDF

Save or share this term-specific reference, including the answer-first definition, engineering review considerations, and primary-source references.

Download the Diagnostic Coverage PDF
Scroll to Top